Easement Requirements FAQ
URD Subdivision Easement Requirements
Blanket Easement Requirements:
- Metes and Bounds
- Final Plat
- Recorded Warranty Deed
- Joint Trench Partners need to have layouts completed and uploaded
- Cable and telco should follow trench
Defined Easement Requirements(URD):
- Recorded Plat
- Joint Trench Partners need to have layouts completed and uploaded
- Cable and telco should follow trench
- Standard Easement for URD is 14’ U.E in front or rear of lot (CNP and JT Partner facilities only)
- Side lots for URD is 10’ UE. (Can be split 5’x5’ between lots. Not always applicable depending on adjacent land (i.e. detention reserve))
Defined Easement Requirements (OVH):
- Recorded Plat (if running through subdivision)
- Metes and Bounds if outside subdivision (i.e. Commercial Tract)
- Standard OVH Perimeter Easement is 10’U.E x 21’ ½ A.E.
- Back to Back (Split between lots or property) 10’U.E. x 30’ A.E.
- Need an 30’ “All Weather Access” road when OVH is installed in reserves and/or when we have limited access to overhead poles
Staking Requirement:
- Proper Monumentation (i.e. Road ROW control points, lots pinned and lathed with legible lot corners where OVH will be located)
- Ground to proper elevation grade
- If SROW is staking under a SFB , then a preliminary / unrecorded plat of the section should be provided as well as monumentation indicating the proposed lots/ roads, etc.
Town Home Easement Requirements
- Recorded plat
- Joint Trench Partners need to have layouts completed and posted
- Cable and telco should follow trench
- For Rear lot construction a standard 14’ UE is required
-
For Front lot construction:
- Electric and Gas Only – 5’ x 5’ Split with additional 3’ x 9’ around facilities
- All Joint Trench Partners – 8’ X 8’ split
- If wets are on property and not in private drive, we need a 16’ UE all on the property
- Facilities cannot be placed in reserves described as drainage and/or detention
-
Access easements required for facilities located in the rear of the lot.
- 3’ access for pedestals
- 5’ access for transformers